A Phase Linear Transmission Line Project


Section 3: Transmission Line Optimization




Figure 3.1a. shows the response of the empty transmission line together with the driver near field response. We can see the first null very clearly around 140 Hz. The fundamental resonance is then about 70 Hz, corresponding to a physical line length of around 1.2 m. The hump at 30 Hz stems from the driver Fs.

Gradually, stuffing was added to the line and the driver and port output was measured. From the measurements, the following observations were made :
  • The LF augmentation is present from 30 Hz (driver Fs) up to 120 Hz. If we compare this with the phase plots, we see that this happens in the region where the phase difference for the driver and port is in the -90 to +90 degree area (Figure 3.1c). The driver has the least amount of phase shift.

  • Adding stuffing, straightens out the amplitude and phase while reducing the amplitude of the first null. The -90 degree difference frequency shifts sligthly downwards in frequency.

  • For low stuffing densities, both the driver NF response and the port response changes as stuffing is added.

  • Above 150 g, the driver NF response stays the same (Figure 3.5)

  • The system phase sum changes up to around 200 g, above this the phase does not straighten out any more (Figure 3.6

  • Stuffing more than 200 g, port output is dampened (Figure 3.4b), reducing the summed output without improving the phase response to any significant degree (Figure 3.6).

  • The optimum stuffing could be defined as getting the most gain possible from the port with as straight as possible phase response. In our case, this is found to be for a stuffing weight of 200 g.

  • More stuffing (250-300 g) might be added if the LF response is too much for the listening room in question. 


Figure 3.1. Empty transmission line | Figure 3.1a. Driver and Sum | Figure 3.1b. Driver and Port NF | Figure 3.1c. Driver and Port phase


opti4_tn.gif (9494 bytes)

(a)

opti5_tn.gif (11985 bytes)

(b)

opti6_tn.gif (9494 bytes)

(c)

Figure 3.2. 100 g transmission line | Figure 3.2a. Driver and Sum. | Figure 3.2b. Driver and Port NF.| Figure 3.2c. Driver and Port phase.


opti7_tn.gif (9494 bytes)

(a)

opti8_tn.gif (11985 bytes)

(b)

opti9_tn.gif (9494 bytes)

(c)

Figure 3.3. 200g transmission line | Figure 3.3a. Driver and Sum| Figure 3.3b. Driver and Port NF | Figure 3.3c. Driver and Port phase.


opti10_tn.gif (9494 bytes)

(a)

opti11_tn.gif (11985 bytes)

(b)

opti12_tn.gif (9494 bytes)

(c)

Figure 3.4. 250g transmission line| Figure 3.4a. Driver and Sum. | Figure 3.4b. Driver and Port NF. | Figure 3.4c. Driver and Port phase.


opti13_tn.gif (9494 bytes)

Figure 3.5. Driver NF -- 150g and 250g.


opti14_tn.gif (11985 bytes)

Figure 3.6. System Phase sum -- 200g and 250g.


 


[ Contents | Intro | Measurements | TL Optimization | Integration | Step Compensation | Time AlignConstruction ]